A Smart Sensing Method for Real- Time Monitoring of Low Voltage Series-Arc-Fault

  • Autori: Ala G.; Artale G.; Cataliotti A.; Cosentino V.; Fontana C.; Romano P.; Viola F.
  • Anno di pubblicazione: 2020
  • Tipologia: Contributo in atti di convegno pubblicato in volume
  • OA Link: http://hdl.handle.net/10447/434696

Abstract

This paper proposes a smart sensing method for real-time monitoring of low voltage series arc fault. It is based on the wavelet coefficient mean-difference algorithm and the four spikes appearing within two fundamental periods criterion with adaptive threshold. The method also uses the hard thresholding wavelet denoising with the universal threshold. An arc fault factor and a load adaptation factor are introduced and combined with a correction factor, so allowing the selection of the adaptive threshold in real-time and the series arc fault detection.