Photovoltaic power forecasting and anomaly detection: a comparative study of statistical, deep learning, and zero-shot foundation models on seven years of real plant data
- Autori: Guarino, S.; Buscemi, A.; Lo Brano, V.
- Anno di pubblicazione: 2026
- Tipologia: Articolo in rivista
- OA Link: http://hdl.handle.net/10447/715103
Abstract
Faults and gradual performance degradation in photovoltaic plants often remain undetected, causing energy losses and increasing maintenance costs. Selecting an appropriate forecasting model for residual-based anomaly detection requires understanding the relative contributions of model architecture and sensor availability; a question not yet addressed by systematic benchmarks on long-term real data. This paper presents a controlled two-phase benchmark based on seven years of real 15-minute PV production data from a grid-connected plant with two synchronised inverters. Four models are evaluated: a multiplicative Prophet model, a Seasonal Autoregressive Integrated Moving Average model with exogenous regressors, a bidirectional Long Short-Term Memory network, and Chronos-2, a zero-shot foundation model requiring no fine-tuning on plant-specific data. In Phase 1, models use only historical production data. In Phase 2, plane-of-array irradiance and module temperature are added as real-time covariates. With covariates, all models exceed R2 = 0.97, enabling a shared three-stage anomaly detection pipeline to identify five operationally distinct fault categories, including inverter blackouts, partial faults, and snow accumulation. Across the test year, two confirmed fault events are identified: a total blackout with an estimated energy loss of 80 kWh and a partial fault with a loss of 21 kWh; the blackout is detected by all models. Zero-shot spatial transfer of the Prophet model to the second inverter achieves R2 = 0.966, outperforming full retraining. Results show that covariate availability has a greater impact on forecast accuracy than model architecture itself. In covariate-rich settings, higher forecast accuracy corresponds to reduced anomaly detection sensitivity. The findings demonstrate that zero-shot foundation models are ready for deployment in PV plants lacking historical data, enabling scalable intelligent monitoring without upfront training.