Salta al contenuto principale
Passa alla visualizzazione normale.

SALVATORE FAVUZZA

Optimal reconfiguration of weakly meshed distribution systems

  • Autori: Augugliaro, A; Dusonchet, L; Favuzza, S; Ippolito, M G; Riva Sanseverino, E
  • Anno di pubblicazione: 2011
  • Tipologia: eedings
  • OA Link: http://hdl.handle.net/10447/60535

Abstract

In this paper the problem of optimal reconfiguration for weakly meshed systems is dealt with; meshes are created by the presence of Favoured Customers (FC) requiring supply through two different paths in order to guarantee the maximum service continuity. Aim of the reconfiguration is to attain a network that operates with minimum power losses, and in order to account for particular needs of the FC loads, that shows the minimum overall yearly fault rate on the branches where the power required by the loads flows. Moreover the constraints concerning the bus voltage profiles, the current in branches and the power balance among HV/MV transformers supplying the network must be full-filled. Due to the intrinsic nature of the problem, for its solution a Genetic Algorithm has been adopted creating some perturbation operators that, differently from existing and well-known perturbation operators, allows to widely explore the search space still keeping the feasibility of solutions.